 | Description |
LoWatt T-Series panel/ceiling models are suitable for mounting at any angle in internal partitions, ceilings, ducts and, with louvred grilles, through external walls. When installed only the louvred grille is visible.
 | Instantaneous Shutter |
With energy saving in mind LoWatt T-Series models are supplied complete with an integral instantaneous automatic louvre shutter concealed behind the interior grille. With a LoWatt T-Series Controller the fan will operate on both extract and intake, suitable for any angle of mounting. The shutter is electronically controlled by an actuator with a damped action giving quiet operation during instant opening and closing. The interlocking edges of the shutter blades provide maximum backdraught protection, when the ventilating unit is used with a LoWatt T-Series controller.
 | Wire-less Control |
Every LoWatt T-Series Wire-less FM Controller uses unique digital signals to ensure trouble free operation. The controller will transmit through walls and floors allowing complete flexibility of design to control fans up to 30m away.
Wire-less FM Controllers can dramatically reduce installation time and costs. The Immediate benefit being the elimination of unsightly wiring. Wire-less FM Controllers can be easily installed in an variety of applications including assembly rooms, banks, hospitals, laboratories, restaurants, schools, shops and public houses.
 | Ceiling |

LoWatt T-Series Panel models are suitable for use in partition walls and ceilings. Supplied complete with fixing screws.
 | Electrical |
Suitable for operation in ambient temperatures from -10°C to +50°C. Fitted with mains resetting software controlled protection. Supply voltage: 220-240V/1/50Hz.
 | NEW LoWatt T-Series Controller |
LoWatt T-Series Controllers are available in both Wired and Wire-less FM versions. The three speed push button surface mounted controllers provide intake/extract and shutter only options and auto mode position for use with external sensors.
Wired versions are connected to the fan using a plug-in Safety Extra Low Voltage
2-core signal cable supplied (10m), allowing simple and safe installation. Alternatively, the Wire-less FM controller offers full control without the need for any wiring, ideal for premises where installations need to be carried out with minimum disruption or where surface wiring can be classed as unsightly or obtrusive.
 | Sensors |
Can be used in conjunction with a LoWatt T-Series Controller
Ambient Response Humidity Sensor - Self programming electronic On/Off wall mounted humidity sensor which reacts to any rapid increase in humidity and temperature. Night time RH increment setback feature
Ecotronic Humidity Sensor - Adjustable set point, solid state controller. Pullcord provides manual override. Adjustable from 65% to 90%RH.
Air Quality Sensor - Automatically reacts to the depletion of air quality, sensing tobacco smoke, smells and toilet odours to regulate mechanically ventilated areas
 | Performance |
|
Unit Size
|
LoWatt TX9PL Wireless
|
LoWatt TX9PL
|
| Stock Ref. No.
|
45 61 71
|
45 61 67
|
| Amps @ 240V
| 0.33
| 0.33
|
Extract Performance m³/h
| Low
| 357
| 357
|
| Med
| 601
| 601
|
| High
| 799
| 799
|
| Watts (high)
| 30
| 30
|
| dB(A) (med) @ 3m
| 41
| 41
|

|
Unit Size
|
LoWatt TX12PL Wireless
|
LoWatt TX12PL
|
| Stock Ref. No.
|
45 61 79
|
45 61 75
|
| Amps @ 240V
| 0.70
| 0.70
|
Extract Performance m³/h
| Low
| 737
| 737
|
| Med
| 1481
| 1481
|
| High
| 1761
| 1761
|
| Watts (high)
| 67
| 67
|
| dB(A) (med) @ 3m
| 48
| 48
|
Recommended controller:
Wire-less Controller Stock Ref. No. 45 58 74
Wired Controller Stock Ref. No. 45 58 73
 | Dimensions (mm) |

| Size
| A
| B
| C
| D
| E
| F
| G
| H
| J
| K
| L
| M
| Weight kg
|
| 230mm
| 391
| 388
| 129
| 39
| 302
| 304
| 255
| 247
| 345
| 309
| 326
| 126
| 5.13
|
| 300mm
| 470
| 467
| 152
| 41
| 378
| 381
| 334
| 325
| 422
| 386
| 402
| 164
| 7.44
|
|